HVI Conductor for tube outside, stranded preassembled D 20mm Cu L 6.0m grey
Kód: 819227Detailní popis produktu
HVI Conductor (high-voltage-resistant, insulated down conductor) for keeping the separation distance from conductive parts according to IEC 62305-3, to prevent dangerous flashover between parts of the external lightning protection system and indoor conductive parts (electrical installation, pipes, etc.). In order to avoid creeping discharge, the HVI Conductor has a special outer sheath which makes it possible to discharge high lightning impulse voltages to a reference potential. HVI Conductor (preassembled, for installation outside of tube, black), with one head piece and one earth connecting element. Equivalent separation distance s ≤ 75 cm (in air), s ≤ 150 cm (solid material).Doplňkové parametry
Kategorie: | Import |
---|---|
Hmotnost: | 3.9 kg |
EAN: | 4013364157712 |
Conductor cross section: | 19 |
Diameter conductor: | 5 |
Farba: | Šedá |
Materiál izolácie: | Polyetylén (PE) |
Materiál plášťa: | XLPE (VPE) |
Materiál vodiča: | Meď |
Max. equivalent separation distance s (in air): | 0.75 |
Max. equivalent separation distance s (solid building materials): | 1.5 |
Max. tensile load: | 950 |
Number of strands: | 1 |
Outer diameter incl. sheat/cover: | 23 |
Použitie vo výbušnom prostredí: | Ano |
Povrch: | Bez ošetrenia |
Trieda vodiča: | Tr. 2 = viacdrôtové |
Vysokonapäťovo stabilné izolované vyhotovenie: | Ano |
Weight: | 66.6 |
Buďte první, kdo napíše příspěvek k této položce.